OC_0780.gsd - OC_0780.gsd PRT1-SCU11 PROFIBUS DP Gateway to Compoway-F / K-Format / Host Link / Memobus protocols
W01E-EN-01.pdf - OPERATION MANUAL PROFIBUS-DP Gateway to Host Link/Compoway-F PRT1-SCU11
;******************************************************************************
;** **
;** Omron Europe B.V. **
;** **
;** European Headquarters **
;** Wegalaan 67-69 **
;** NL-2132 JD Hoofddorp **
;** The Netherlands **
;** **
;** Automation Business Unit **
;** Zilverenberg 2 **
;** NL-5234 GM 's-Hertogenbosch **
;** The Netherlands **
;** **
;******************************************************************************
;** **
;** Device DataBase File for PRT1-SCU11 **
;** **
;** Filename: OC_0780.GSD **
;** Version : 3.6 **
;** Date : July 7th, 2005 **
;** **
;** (C) Copyright OMRON Corporation 2005 **
;** All Rights Reserved **
;** **
;******************************************************************************
;** **
;** Important notice: **
;** ================== **
;** - Any modification of parameters in this file may lead to undefined **
;** behavior of the Profibus-DP system. **
;** **
; General information ********************************************************/
;------------------------------------------------------------------------------
; DP-Parameter
;------------------------------------------------------------------------------
#Profibus_DP
GSD_Revision = 2
Vendor_Name = "OMRON Corporation"; Manufacturer
Model_Name = "PRT1-SCU11" ; Name of device
Ident_Number = 0x0780 ; Ident-Number
FMS_supp = 0 ; No DP-/FMS-mixed operation
Protocol_Ident = 0 ; PROFIBUS_DP Protocol
Station_Type = 0 ; Slave-Station
Slave_Family = 9 ; Gateway
Revision = "V3.6" ; Revision of GSD file
Hardware_Release = "V1.0" ; Hardware Revision
Software_Release = "V2.0" ; Firmware Revision 2.0
;------------------------------------------------------------------------------
; Specific implementation information
;------------------------------------------------------------------------------
Implementation_type = "SPC3" ; DP protocol.
Redundancy = 0 ; not supported
Repeater_Ctrl_Sig = 0 ; not supported
24V_Pins = 0 ; not supported
Set_Slave_Add_supp = 0 ; Station address is set
; through hardware address
; selectors
;------------------------------------------------------------------------------
; Media access information
;------------------------------------------------------------------------------
Auto_Baud_supp = 1 ; supported
9.6_supp = 1 ; Baud Rate 9.6kB supported
19.2_supp = 1 ; Baud Rate 19.2kB supported
93.75_supp = 1 ; Baud Rate 93.75kB supported
45.45_supp = 1 ; Baud Rate 45.45kB supported
187.5_supp = 1 ; Baud Rate 187.5kB supported
500_supp = 1 ; Baud Rate 500kB supported
1.5M_supp = 1 ; Baud Rate 1.5MB supported
3M_supp = 1 ; Baud Rate 3MB supported
6M_supp = 1 ; Baud Rate 6MB supported
12M_supp = 1 ; Baud Rate 12MB supported
;
MaxTsdr_9.6 = 60 ; 60 Tbit = 6.25 msec.
MaxTsdr_19.2 = 60 ; 60 Tbit = 3.125 msec.
MaxTsdr_45.45 = 250 ; 250 Tbit = 5.50 msec.
MaxTsdr_93.75 = 60 ; 60 Tbit = 640 usec.
MaxTsdr_187.5 = 60 ; 60 Tbit = 320 usec.
MaxTsdr_500 = 100 ; 100 Tbit = 200 usec.
MaxTsdr_1.5M = 150 ; 150 Tbit = 100 usec.
MaxTsdr_3M = 250 ; 250 Tbit = 83 usec.
MaxTsdr_6M = 450 ; 450 Tbit = 75 usec.
MaxTsdr_12M = 800 ; 800 Tbit = 67 usec.
;
;------------------------------------------------------------------------------
; DP-slave information
;------------------------------------------------------------------------------
Freeze_Mode_supp = 1 ; supported
Sync_Mode_supp = 1 ; supported
Fail_Safe = 1 ; Fail safe supported.
;
Modular_Station = 1 ; Modular Device
Max_Module = 18 ; Max. No of Modules -
; 15 stations + 3x Free Comms Blocks
Max_Input_Len = 200 ; Max. Input Data Length
Max_Output_Len = 200 ; Max. Output Data Length
Max_Data_Len = 400 ; Max. Data Length I/O together
Min_Slave_Intervall = 5 ; at max. all 500us a new data_exchange
; Telegramm
;------------------------------------------------------------------------------
; Definition of Extended Diag Data bytes in Response of slave_diag:
;------------------------------------------------------------------------------
Max_Diag_Data_Len = 16 ; Maximum diagnostic length
;
Unit_Diag_Bit(0) = "Communication Error with Node 1"
Unit_Diag_Bit(1) = "Communication Error with Node 2"
Unit_Diag_Bit(2) = "Communication Error with Node 3"
Unit_Diag_Bit(3) = "Communication Error with Node 4"
Unit_Diag_Bit(4) = "Communication Error with Node 5"
Unit_Diag_Bit(5) = "Communication Error with Node 6"
Unit_Diag_Bit(6) = "Communication Error with Node 7"
Unit_Diag_Bit(7) = "Communication Error with Node 8"
Unit_Diag_Bit(8) = "Communication Error with Node 9"
Unit_Diag_Bit(9) = "Communication Error with Node 10"
Unit_Diag_Bit(10) = "Communication Error with Node 11"
Unit_Diag_Bit(11) = "Communication Error with Node 12"
Unit_Diag_Bit(12) = "Communication Error with Node 13"
Unit_Diag_Bit(13) = "Communication Error with Node 14"
Unit_Diag_Bit(14) = "Communication Error with Node 15"
Unit_Diag_Bit(15) = "Communication Error with Node 16"
Unit_Diag_Bit(16) = "Communication Error with Node 17"
Unit_Diag_Bit(17) = "Communication Error with Node 18"
Unit_Diag_Bit(18) = "Communication Error with Node 19"
Unit_Diag_Bit(19) = "Communication Error with Node 20"
Unit_Diag_Bit(20) = "Communication Error with Node 21"
Unit_Diag_Bit(21) = "Communication Error with Node 22"
Unit_Diag_Bit(22) = "Communication Error with Node 23"
Unit_Diag_Bit(23) = "Communication Error with Node 24"
Unit_Diag_Bit(24) = "Communication Error with Node 25"
Unit_Diag_Bit(25) = "Communication Error with Node 26"
Unit_Diag_Bit(26) = "Communication Error with Node 27"
Unit_Diag_Bit(27) = "Communication Error with Node 28"
Unit_Diag_Bit(28) = "Communication Error with Node 29"
Unit_Diag_Bit(29) = "Communication Error with Node 30"
Unit_Diag_Bit(30) = "Communication Error with Node 31"
Unit_Diag_Area = 32-47
Value (0) = "System OK"
Value (262) ="System Error Code"
Unit_Diag_Area_End
;------------------------------------------------------------------------------
; Parameter Text Definition List
;------------------------------------------------------------------------------
PrmText = 1
Text(0) = "Hold Last Value"
Text(1) = "Send Stop"
EndPrmText
PrmText = 2
Text(0)="OFF (default)"
Text(4)="ON"
EndPrmText
;------------------------------------------------------------------------------
; Extended User Parameter Text Definition List
;------------------------------------------------------------------------------
ExtUserPrmData = 1 "Output data on PROFIBUS Fail"
Bit(7) 0 0-1
Prm_Text_Ref = 1
EndExtUserPrmData
ExtUserPrmData = 2 "Fail-Safe support"
BitArea(4-7) 0 0,4
Prm_Text_Ref = 2
EndExtUserPrmData
ExtUserPrmData = 3 "Device Address"
BitArea(0-4) 1 1-31
EndExtUserPrmData
ExtUserPrmData = 4 "Read Register Address One"
Unsigned16 0x0020 0x0000-0xFFFF
EndExtUserPrmData
ExtUserPrmData = 5 "Read Register Address Two"
Unsigned16 0x0023 0x0000-0xFFFF
EndExtUserPrmData
ExtUserPrmData = 6 "Read Register Address Three"
Unsigned16 0x0025 0x0000-0xFFFF
EndExtUserPrmData
ExtUserPrmData = 7 "Write Register Address One"
Unsigned16 0x0001 0x0000-0xFFFF
EndExtUserPrmData
ExtUserPrmData = 8 "Write Register Address Two"
Unsigned16 0x0002 0x0000-0xFFFF
EndExtUserPrmData
ExtUserPrmData = 9 "Write Register Address Three"
Unsigned16 0x0003 0x0000-0xFFFF
EndExtUserPrmData
ExtUserPrmData = 10 "Read Status Register"
Unsigned16 0x0020 0x0020-0x0020
EndExtUserPrmData
ExtUserPrmData = 11 "Read Frequency Register"
Unsigned16 0x0023 0x0023-0x0023
EndExtUserPrmData
ExtUserPrmData = 12 "Read Voltage Register"
Unsigned16 0x0025 0x0025-0x0025
EndExtUserPrmData
ExtUserPrmData = 13 "Write Command Register"
Unsigned16 0x0001 0x0001-0x0001
EndExtUserPrmData
ExtUserPrmData = 14 "Write Frequency Register"
Unsigned16 0x0002 0x0002-0x0002
EndExtUserPrmData
ExtUserPrmData = 15 "Write Voltage Register"
Unsigned16 0x0003 0x0003-0x0003
EndExtUserPrmData
;------------------------------------------------------------------------------
; Extended User Param Data
;------------------------------------------------------------------------------
Max_User_Prm_Data_Len = 228
Ext_User_Prm_Data_Const(0) = 0x00,0x00,0x00,0x00 ; 4 Bytes reserved
; UserPrmData
Ext_User_Prm_Data_Ref(0) = 2
;------------------------------------------------------------------------------
; Empty slot module
;------------------------------------------------------------------------------
Module= "Empty Slot (No Device - 0WI/0WO)" 0x00
1
EndModule
;------------------------------------------------------------------------------
; E5ZN Fixed I/O Configuration module definitions
;------------------------------------------------------------------------------
Module = "E5ZN-Basic 2 Channel 2WI/2WO" 0xF1
2
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x01
Ext_User_Prm_Data_Ref(0) = 1
EndModule
Module = "E5ZN-Extended 2 Channel 11WI/3WO" 0xE2, 0xDA
3
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x02
Ext_User_Prm_Data_Ref(0) = 1
EndModule
;------------------------------------------------------------------------------
; E5_N Fixed I/O Configuration module definitions
;------------------------------------------------------------------------------
Module = "E5_N-Basic 1WI/1WO" 0xF0
4
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x03
Ext_User_Prm_Data_Ref(0) = 1
EndModule
Module = "E5_N-Extended 6WI/2WO" 0xE1, 0xD5
5
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x04
Ext_User_Prm_Data_Ref(0) = 1
EndModule
;------------------------------------------------------------------------------
; E5_R Fixed I/O Configuration module definitions
;------------------------------------------------------------------------------
Module = "E5_R-Basic 1 Channel 1WI/1WO" 0xF0
6
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x05
Ext_User_Prm_Data_Ref(0) = 1
EndModule
Module = "E5_R-Basic 2 Channel 2WI/2WO" 0xF1
7
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x06
Ext_User_Prm_Data_Ref(0) = 1
EndModule
Module = "E5_R-Basic 4 Channel 4WI/4WO" 0xF3
8
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x07
Ext_User_Prm_Data_Ref(0) = 1
EndModule
Module = "E5_R-Extended 1 Channel 6WI/2WO" 0xE1, 0xD5
9
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x08
Ext_User_Prm_Data_Ref(0) = 1
EndModule
Module = "E5_R-Extended 2 Channel 11WI/3WO" 0xE2, 0xDA
10
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x09
Ext_User_Prm_Data_Ref(0) = 1
EndModule
Module = "E5_R-Extended 4 Channel 21WI/5WO" 0xE4, 0xDF, 0xD4
11
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x0A
Ext_User_Prm_Data_Ref(0) = 1
EndModule
;------------------------------------------------------------------------------
; E5_K Fixed I/O Configuration module definitions
;------------------------------------------------------------------------------
Module = "E5_K-Basic 5WI/2WO" 0xE1, 0xD4
12
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x0B
Ext_User_Prm_Data_Ref(0) = 1
EndModule
Module = "E5_K-Extended 5WI/4WO" 0xE3, 0xD4
13
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x0C
Ext_User_Prm_Data_Ref(0) = 1
EndModule
;------------------------------------------------------------------------------
; E5_N/E5ZN/E5_R Free Communication I/O Configuration module definitions
;------------------------------------------------------------------------------
Module = "E5_N/E5_R FC-read 4WI/5WO" 0xE4, 0xD3
16
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x20
EndModule
Module = "E5_N/E5_R FC-write 2WI/7WO" 0xE6, 0xD1
17
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x21
EndModule
Module = "E5_N/E5_R FC-operate 2WI/3WO" 0xE2, 0xD1
18
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x22
EndModule
;------------------------------------------------------------------------------
; E5_K Free Communication I/O Configuration module definitions
;------------------------------------------------------------------------------
Module = "E5_K FC-read/write/spec 3WI/3WO" 0xF2
19
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x23
EndModule
;------------------------------------------------------------------------------
; R88A-MCW151-E Fixed I/O Configuration module definitions
;------------------------------------------------------------------------------
Module = "MCW151 Host Link 5WI/5WO" 0xF4
20
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x40
EndModule
Module = "MCW151 Host Link 10WI/10WO" 0xF9
21
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x41
EndModule
Module = "MCW151 Host Link 15WI/15WO" 0xFE
22
Ext_Module_Prm_Data_Len = 1
Ext_User_Prm_Data_Const(0) = 0x42
EndModule
;------------------------------------------------------------------------------
; Memobus Fixed I/O Configuration module definitions
;------------------------------------------------------------------------------
Module = "Memobus Fixed 3WI/3WO" 0xF2
23
Ext_Module_Prm_Data_Len = 13
Ext_User_Prm_Data_Const(0) = 0xE0
Ext_User_Prm_Data_Ref(0) = 3
Ext_User_Prm_Data_Ref(1) = 10
Ext_User_Prm_Data_Ref(3) = 11
Ext_User_Prm_Data_Ref(5) = 12
Ext_User_Prm_Data_Ref(7) = 13
Ext_User_Prm_Data_Ref(9) = 14
Ext_User_Prm_Data_Ref(11) = 15
EndModule
Module = "Memobus 3WI/3WO" 0xF2
24
Ext_Module_Prm_Data_Len = 13
Ext_User_Prm_Data_Const(0) = 0x60
Ext_User_Prm_Data_Ref(0) = 3
Ext_User_Prm_Data_Ref(1) = 4
Ext_User_Prm_Data_Ref(3) = 5
Ext_User_Prm_Data_Ref(5) = 6
Ext_User_Prm_Data_Ref(7) = 7
Ext_User_Prm_Data_Ref(9) = 8
Ext_User_Prm_Data_Ref(11) = 9
EndModule |