SIEMENS SINAMICS G: load distribution using direct data exchange with SINAMICSG120/G120C/G120D SIMATIC S7 300/400

SIEMENS SINAMICS G: load distribution using direct data exchange

60602336_sinamics-g_querverkehr_leit-folgeantrieb_v1-1_en.pdf - SINAMICS G: load distribution using direct data exchange with SINAMICSG120/G120C/G120D SIMATIC S7 300/400

Code script for the master - 60602336_script_master_v11.zip - txt file

Code script for the slave - 60602336_script_slave_v11.zip -  txt file

Code SIMATIC project - 60602336_SIMATIC-Project_V1-1.zip - STEP7

June 2013 

_script_master_v11.txt


'script_master_V 1.0 Uttinger 2012-05-15
'V1.1              MeЯner   2013-04-17   
'
APP.LogActive = True        ' Ausgabe aktivieren
'
On Error Resume Next
Parameters(922, 0) = 1               'PROFIdrive PZD Telegrammauswahl
Parameters(922, 0) = 999                'PROFIdrive PZD Telegrammauswahl
Parameters(2051, 0) = "2089:0:63"       'CI: PROFIdrive PZD senden Wort, PZD 1
Parameters(2051, 1) = "63:0:63"         'CI: PROFIdrive PZD senden Wort, PZD 2
Parameters(2051, 2) = "79:0:63"         'CI: PROFIdrive PZD senden Wort, PZD 3
Parameters(2051, 3) = "52:0:63"         'CI: PROFIdrive PZD senden Wort, PZD 4
Parameters(2051, 4) = "0"               'CI: PROFIdrive PZD senden Wort, PZD 5
Parameters(2051, 5) = "0"               'CI: PROFIdrive PZD senden Wort, PZD 6
Parameters(2051, 6) = "0"               'CI: PROFIdrive PZD senden Wort, PZD 7
Parameters(2051, 7) = "0"               'CI: PROFIdrive PZD senden Wort, PZD 8
Parameters(2051, 8) = "0"               'CI: PROFIdrive PZD senden Wort, PZD 9
Parameters(2051, 9) = "0"               'CI: PROFIdrive PZD senden Wort, PZD 10
Parameters(2051, 10) = "0"              'CI: PROFIdrive PZD senden Wort, PZD 11
Parameters(2051, 11) = "0"              'CI: PROFIdrive PZD senden Wort, PZD 12
Parameters(1503, 0) = "0"               'CI: Drehmomentsollwert
Parameters(1503, 1) = "0"               'CI: Drehmomentsollwert
Parameters(1552, 0) = "1"               'CI: Drehmomentgrenze oben Skalierung ohne Offset
Parameters(1552, 1) = "1"               'CI: Drehmomentgrenze oben Skalierung ohne Offset
Parameters(1554, 0) = "1"               'CI: Drehmomentgrenze unten Skalierung ohne Offset
Parameters(1554, 1) = "1"               'CI: Drehmomentgrenze unten Skalierung ohne Offset
On Error GoTo 0


_script_slave_v11.txt


'script_slaveV 1.0 Uttinger 2012-05-15
'V1.1              MeЯner   2013-04-17      
'
APP.LogActive = True        ' Ausgabe aktivieren
'
On Error Resume Next
Parameters(922, 0) = 1                  'PROFIdrive PZD Telegrammauswahl
Parameters(1501, 0) = "2090:15:63"      'BI: Drehzahl-/Drehmomentregelung umschalten
Parameters(1501, 1) = "0"               'BI: Drehzahl-/Drehmomentregelung umschalten
Parameters(1503, 0) = "2050:2:63"       'CI: Drehmomentsollwert
Parameters(1503, 1) = "0"               'CI: Drehmomentsollwert
On Error GoTo 0


 