ARIS PMR2 PROFIBUS DC GSD
ARIS06EE.GSD
aris06EF.GSD
;********************* GSD-Datei ARIS PMR2 PROFIBUS DC ******************************
;* ================================================================================ *
;* *
;* ARIS Antriebe und Steuerungen GmbH *
;* LцhestraЯe 18 *
;* 53773 Hennef / Germany *
;* Fon: +49 2242 91362 0 *
;* Fax: +49 2242 91362 99 *
;* aris@stellantriebe.de *
;* www.stellantriebe.de *
;* *
;* ================================================================================ *
;* *
;* *
;************************************************************************************
;
#Profibus_DP
;
;
; <Unit-Definition-List>
GSD_Revision = 2
Vendor_Name="ARIS Antriebe & Steuerungen GmbH"
Model_Name = "PMR-PB-DC"
Revision = "1.0"
Ident_Number=0x06EE
Protocol_Ident = 0
Station_Type = 0
FMS_supp = 0
Hardware_Release = "1.00"
Software_Release = "1.00"
;
9.6_supp = 1
19.2_supp = 1
45.45_supp = 1
93.75_supp = 1
187.5_supp = 1
500_supp = 1
1.5M_supp = 1
3M_supp = 1
6M_supp = 1
12M_supp = 1
MaxTsdr_9.6 = 60
MaxTsdr_19.2 = 60
MaxTsdr_45.45 = 60
MaxTsdr_93.75 = 60
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 450
MaxTsdr_12M = 800
;
Redundancy = 0
Repeater_Ctrl_Sig = 2
24V_Pins = 0
Implementation_Type = "VPC3"
Bitmap_Device = "aris_pmr"
;
Unit_Diag_Bit(0)= "Error: Parameter Data Length"
Unit_Diag_Bit(1)= "Error: Parameter Data Entry"
Unit_Diag_Bit(2)= "Error: Configuration Data Length"
Unit_Diag_Bit(3)= "Error: Configuration Data Entry"
;
Freeze_Mode_supp = 1
Sync_Mode_supp = 1
Auto_Baud_supp = 1
Set_Slave_Add_supp = 0
Min_Slave_Intervall = 6
Modular_Station=1
Max_Module=1
Max_Input_Len=12
Max_Output_Len=9
Max_Data_Len=21
Fail_Safe = 1
;
Max_Diag_Data_Len = 8
Modul_Offset = 0
Slave_Family = 3@Profichip@VPC3
;
; **************** PARAMTER Definition
; Prm-Text-Def-List:
;
PrmText = 1
Text(0) = "AUS"
Text(1) = "EIN"
EndPrmText
;
PrmText = 2
Text(0) = "AUS"
Text(1) = "Einfaches Sicherheitsverhalten"
Text(2) = "Erweitertes Sicherheitsverhalten"
EndPrmText
;
PrmText = 3
Text(0) = "Antrieb STOP"
Text(1) = "Antrieb AUF"
Text(2) = "Antrieb ZU"
Text(3) = "Antrieb POSITION"
EndPrmText
;
;
;User_Prm_Data_Definition 1
ExtUserPrmData = 1 "RESERVIERT"
Unsigned8 0 0-0
EndExtUserPrmData
;
;User_Prm_Data_Definition 2
ExtUserPrmData = 2 "Hysterese AUS in Promille"
Unsigned8 2 0-255
EndExtUserPrmData
;
;User_Prm_Data_Definition 3
ExtUserPrmData = 3 "Hysterese EIN in Promille"
Unsigned8 5 0-255
EndExtUserPrmData
;
;User_Prm_Data_Definition 4
ExtUserPrmData = 4 "Nachlaufzeit in 20ms"
Unsigned8 1 0-255
EndExtUserPrmData
;
;User_Prm_Data_Definition 5
ExtUserPrmData = 5 "Drehrichtungsueberwachung"
Unsigned8 0 0-1
Prm_Text_Ref = 1
EndExtUserPrmData
;
;User_Prm_Data_Definition 6
ExtUserPrmData = 6 "Blockierschutz"
Unsigned8 0 0-1
Prm_Text_Ref = 1
EndExtUserPrmData
;
;User_Prm_Data_Definition 7
ExtUserPrmData = 7 "Temperaturschwelle"
Signed8 80 -40-120
EndExtUserPrmData
;
;User_Prm_Data_Definition 8
ExtUserPrmData = 8 "Sicherheitsverhalten"
Unsigned8 0 0-2
Prm_Text_Ref = 2
EndExtUserPrmData
;
;User_Prm_Data_Definition 9
ExtUserPrmData = 9 "Ausloesezeit in 10s"
Unsigned8 1 0-255
EndExtUserPrmData
;
;User_Prm_Data_Definition 10
ExtUserPrmData = 10 "Sicherheitsfahrt"
Unsigned8 0 0-3
Prm_Text_Ref = 3
EndExtUserPrmData
;
;User_Prm_Data_Definition 11
ExtUserPrmData = 11 "Sicherheitsposition in Promille"
Unsigned16 0 0-1000
EndExtUserPrmData
;
Max_User_Prm_Data_Len = 12
;
; Ext-User-Prm-Data-Def-List:
Ext_User_Prm_Data_Ref (0) = 1
Ext_User_Prm_Data_Ref (1) = 2
Ext_User_Prm_Data_Ref (2) = 3
Ext_User_Prm_Data_Ref (3) = 4
Ext_User_Prm_Data_Ref (4) = 5
Ext_User_Prm_Data_Ref (5) = 6
Ext_User_Prm_Data_Ref (6) = 7
Ext_User_Prm_Data_Ref (7) = 8
Ext_User_Prm_Data_Ref (8) = 9
Ext_User_Prm_Data_Ref (9) = 10
Ext_User_Prm_Data_Ref (10) = 11
; <Parameter-Definition-List>
User_Prm_Data_Len = 12
User_Prm_Data = 0x00,0x02,0x05,0x00,0x00,0x00,0x50,0x00,0x01,0x00,0x00,0x00
;
; <Module-Definition-List >
Module="ARIS PMR2" 0x16,0x23
EndModule
Module="ARIS PMR2 + I/O" 0x17,0x24
EndModule
Module="ARIS PMR2 + I/O + ADC" 0x1B,0x28
EndModule
; <Module-Definition-List konsistent>
Module="ARIS PMR2 konsistent" 0x96,0xA3
EndModule
Module="ARIS PMR2 + I/O konsistent" 0x97,0xA4
EndModule
Module="ARIS PMR2 + I/O + ADC konsistent" 0x9B,0xA8
EndModule |