krft094b.gsd
;
;********************* GSD-Datei for Kraft PPR **************************
;* ================================================================================ *
;* *
;* -------------------------------------------------------------------------------- *
;* author: R. Andersson date: 2004-11-25 *
;* rev.: 001 *
;* -------------------------------------------------------------------------------- *
;* *
;* history *
;* ================================================================================ *
;* 2004-11-25 Final Version 1 *
;* 2005-05-13 Buadrate upgrade to 12 Mbit *
;* -------------------------------------------------------------------------------- *
;* *
;************************************************************************************
;
;
#Profibus_DP
;
;
; <Unit-Definition-List>
GSD_Revision = 1
Vendor_Name = "Kraftelektronik AB"
Model_Name = "Flex Kraft"
Revision = "1.2"
Ident_Number = 0x094b
Protocol_Ident = 0
Station_Type = 0
FMS_supp = 0
Hardware_Release = "V100"
Software_Release = "1.00"
;
9.6_supp = 1
19.2_supp = 1
93.75_supp = 1
187.5_supp = 1
500_supp=1
1.5M_supp=1
3M_supp=1
6M_supp=1
12M_supp=1
MaxTsdr_9.6 = 60
MaxTsdr_19.2 = 60
MaxTsdr_93.75 = 60
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 450
MaxTsdr_12M = 800
;
Redundancy = 0
Repeater_Ctrl_Sig=0
24V_Pins = 0
Implementation_Type = "VPC3+"
;
Unit_Diag_Bit(0)= "Error: Parameter Data Length"
Unit_Diag_Bit(1)= "Error: Parameter Data Entry"
Unit_Diag_Bit(2)= "Error: Configuration Data Length"
Unit_Diag_Bit(3)= "Error: Configuration Data Entry"
;
Freeze_Mode_supp = 1
Sync_Mode_supp = 1
Auto_Baud_supp = 1
Set_Slave_Add_supp = 0
Min_Slave_Intervall = 10
Modular_Station = 1
Max_Module=2
Max_Input_Len=244
Max_Output_Len=244
Max_Data_Len=244
Fail_Safe=1
;
Max_Diag_Data_Len = 16
Modul_Offset = 0
Slave_Family=0@Kraft
;
; <Parameter-Definition-List>
User_Prm_Data_Len = 0
;
; <Module-Definition-List>
Module="FlexKraft Std " 0x5f,0x51,0x68
EndModule
Module="FlexKraft Std Dual" 0x5f,0x59,0x6c
EndModule |