PLC, HMI, SCADA, INVERTERS, TUTORIALS, INDUSTRIAL AUTOMATION

07:46
Pepperl Fuchs WCS-PG210 PROFIBUS PF2079.gsd

PF2079.gsd - PF2079.gsd

#Profibus_DP
; Historie
; Дnderung 26.06.07
; ROP(P+F) Vendor_Name to "Pepperl+Fuchs"
; Slave_Family     from 9 to 9@Pepperl+Fuchs@WCS
; Module Names to reading head
 
GSD_Revision        = 1
;
Vendor_Name         = "Pepperl+Fuchs"
Model_Name          = "WCS-PG210"
Revision            = "V1.5"
Ident_Number        = 0x2079
Protocol_Ident      = 0
Station_Type        = 0
FMS_supp            = 0
Hardware_Release    = "Revision G"
Software_Release    = "V4.43"
OrderNumber        = "WCS-PG210" 
;
9.6_supp            = 1
19.2_supp           = 1
93.75_supp          = 1
187.5_supp          = 1
500_supp            = 1
1.5M_supp           = 1
3M_supp             = 1
6M_supp             = 1
12M_supp            = 1
;
MaxTsdr_9.6         = 60
MaxTsdr_19.2        = 60
MaxTsdr_93.75       = 60
MaxTsdr_187.5       = 60
MaxTsdr_500         = 100
MaxTsdr_1.5M        = 150
MaxTsdr_3M          = 250
MaxTsdr_6M          = 450
MaxTsdr_12M         = 800
;
Redundancy          = 0
Repeater_Ctrl_Sig   = 2
24V_Pins            = 0
Implementation_Type = "SPC3"
;
Freeze_Mode_supp    = 1
Sync_Mode_supp      = 1
Auto_Baud_supp      = 1
Set_Slave_Add_supp  = 0
Min_Slave_Intervall = 1
;
Modular_Station     = 1
Max_Module          = 1
Max_Input_Len       = 244
Max_Output_Len      = 244
Max_Data_Len        = 448
Modul_Offset        = 0
;
Fail_Safe           = 0
Slave_Family        = 9@Pepperl+Fuchs@WCS
Max_Diag_Data_Len   = 8
;
Module             = "WCS: 1 reading head" 0x20,0xD1
1
EndModule
Module             = "WCS: 2 reading heads" 0x20,0xD1,0xD1
2
EndModule
Module             = "WCS: 3 reading heads" 0x20,0xD1,0xD1,0xD1
3
EndModule
Module             = "WCS: 4 reading heads" 0x20,0xD1,0xD1,0xD1,0xD1
4
EndModule
;