DELA08DB.GSD

;==========================================================
; GSD-File  for Delta CMC-PD01

; Auto_Baud_supp, 12MBaud 
;
; Stand : 
; File    : deltpd01.GSD
;=========================================================== 

#Profibus_DP

; Unit-Definition-List:

GSD_Revision        = 1
Vendor_Name         = "Delta Electronics"
Model_Name          = "C2000 DRIVES"
Revision            = "Rev. 1"
Ident_Number        = 0x08DB
Protocol_Ident      = 0        ; PROFIBUS DP
Station_Type        = 0        ; DP-slave
FMS_supp            = 0
Hardware_Release    = "V1.0"
Software_Release    = "V1.0"
Redundancy          = 0
Repeater_Ctrl_Sig   = 2        ; TTL
24V_Pins            = 0
Implementation_Type = "SPC3"
Bitmap_Device       = "VFDDRV"
Bitmap_Diag         = "VFDDRV"
Bitmap_SF           = "VFDDRV"
Slave_Family        = 1@TdF@Delta VFD Drives    ; Drives family

; Supported Communication Speeds:

Auto_Baud_supp      = 1
9.6_supp            = 1
19.2_supp           = 1
93.75_supp          = 1
187.5_supp          = 1
500_supp            = 1
1.5M_supp           = 1
3M_supp             = 1
6M_supp             = 1
12M_supp            = 1
MaxTsdr_9.6         = 60
MaxTsdr_19.2        = 60
MaxTsdr_93.75       = 60
MaxTsdr_187.5       = 60
MaxTsdr_500         = 100
MaxTsdr_1.5M        = 150
MaxTsdr_3M          = 250
MaxTsdr_6M          = 450
MaxTsdr_12M         = 800


; DP_Slave Information:

Freeze_Mode_supp    = 1
Sync_Mode_supp      = 1
Set_Slave_Add_supp  = 0
Min_Slave_Intervall = 1        ; 100 micro-second

; Module-Definitions:

Modular_Station     = 1        ; 0-compact; 1-modular
Max_Module          = 1
Max_Input_Len       = 60
Max_Output_Len      = 60
Max_Data_Len        = 120

Modul_Offset        = 0
Fail_Safe           = 0
Max_Diag_Data_Len   = 16
ORDERNUMBER="PD-01"

;zr modify ok
;specify the user parameters:

 
Max_User_Prm_Data_Len      = 51
User_Prm_Data_Len         = 51
User_Prm_Data            = 0x00,0x00,0x00,\
                 0x20,0x00,\
                             0x20,0x01,\
                             0x00,0x00,\
                             0x00,0x00,\
                 0x00,0x00,\
                 0x00,0x00,\
                 0x00,0x00,\
                 0x00,0x00,\
                 0x00,0x00,\
                 0x00,0x00,\
                             0x21,0x01,\
                             0x21,0x02,\
                             0x21,0x03,\
                             0x21,0x04,\
                 0x00,0x00,\
                 0x00,0x00,\
                 0x00,0x00,\
                 0x00,0x00,\
                 0x00,0x00,\
                 0x00,0x00,\
                             0x00,0x02,\
                             0x00,0x02,\
                             0x00,0x01,\
                             0x00,0x00
;type modify ok zr
Module = "4 PKW,  2  PZD  (PPO 1)        " 0xF3, 0xF1
EndModule
Module = "4 PKW,  6  PZD  (PPO 2)     " 0xF3, 0xF5
EndModule
Module = "0 PKW,  2  PZD  (PPO 3)        " 0x00, 0xF1
EndModule
Module = "0 PKW,  6  PZD  (PPO 4)        " 0x00, 0xF5
EndModule
Module = "4 PKW,  10 PZD  (PPO 5)        " 0xF3, 0xF9
EndModule
Module = "4 PKW,  4  PZD                 " 0xF3, 0xF3
EndModule
Module = "0 PKW,  4  PZD                 " 0x00, 0xF3
EndModule

; Extended Description of User-Parameters

PrmText = 1
Text(0) = "Ignore and Continue"
Text(1) = "Stop accord to Pr.STOP METHOD"
EndPrmText

PrmText = 2
Text(0) = "Stop DataExchange & Report Fault"
Text(1) = "Continue & Report Alarm"
Text(2) = "Ignore & Continue DataExchange"
EndPrmText

ExtUserPrmData = 1 "Data Output 1(CMC-PD01 -> VFD)"
Unsigned16 0x2000 0-65535
EndExtUserPrmData

ExtUserPrmData = 2 "Data Output 2"
Unsigned16 0x2001 0-65535
EndExtUserPrmData

ExtUserPrmData = 3 "Data Output 3"
Unsigned16 0x0000 0-65535
EndExtUserPrmData

ExtUserPrmData = 4 "Data Output 4"
Unsigned16 0x0000 0-65535
EndExtUserPrmData

ExtUserPrmData = 5 "Data Output 5"
Unsigned16 0x0000 0-65535
EndExtUserPrmData

ExtUserPrmData = 6 "Data Output 6"
Unsigned16 0x0000 0-65535
EndExtUserPrmData

ExtUserPrmData = 7 "Data Output 7"
Unsigned16 0x0000 0-65535
EndExtUserPrmData

ExtUserPrmData = 8 "Data Output 8"
Unsigned16 0x0000 0-65535
EndExtUserPrmData

ExtUserPrmData = 9 "Data Output 9"
Unsigned16 0x0000 0-65535
EndExtUserPrmData

ExtUserPrmData = 10 "Data Output 10"
Unsigned16 0x0000 0-65535
EndExtUserPrmData

ExtUserPrmData = 11 "Data Input 1(VFD -> CMC-PD01)"
Unsigned16 0x2101 0-65535
EndExtUserPrmData

ExtUserPrmData = 12 "Data Input 2"
Unsigned16 0x2102 0-65535
EndExtUserPrmData

ExtUserPrmData = 13 "Data Input 3"
Unsigned16 0x2103 0-65535
EndExtUserPrmData

ExtUserPrmData = 14 "Data Input 4"
Unsigned16 0x2104 0-65535
EndExtUserPrmData

ExtUserPrmData = 15 "Data Input 5"
Unsigned16 0x0000 0-65535
EndExtUserPrmData

ExtUserPrmData = 16 "Data Input 6"
Unsigned16 0x0000 0-65535
EndExtUserPrmData

ExtUserPrmData = 17 "Data Input 7"
Unsigned16 0x0000 0-65535
EndExtUserPrmData

ExtUserPrmData = 18 "Data Input 8"
Unsigned16 0x0000 0-65535
EndExtUserPrmData

ExtUserPrmData = 19 "Data Input 9"
Unsigned16 0x0000 0-65535
EndExtUserPrmData

ExtUserPrmData = 20 "Data Input 10"
Unsigned16 0x0000 0-65535
EndExtUserPrmData

ExtUserPrmData = 21 "dout_len"
Unsigned16 2 0-10
EndExtUserPrmData

ExtUserPrmData = 22 "din_len"
Unsigned16 2 0-10
EndExtUserPrmData

ExtUserPrmData = 23 "LossDPComTreat"
Unsigned16 1 0-1
Prm_Text_Ref = 1
EndExtUserPrmData

ExtUserPrmData = 24 "LossSPComTreat"
Unsigned16 0 0-2
Prm_Text_Ref = 2
EndExtUserPrmData

Ext_User_Prm_Data_Ref(3) = 1
Ext_User_Prm_Data_Ref(5) = 2
Ext_User_Prm_Data_Ref(7) = 3
Ext_User_Prm_Data_Ref(9) = 4
Ext_User_Prm_Data_Ref(11) = 5
Ext_User_Prm_Data_Ref(13) = 6
Ext_User_Prm_Data_Ref(15) = 7
Ext_User_Prm_Data_Ref(17) = 8
Ext_User_Prm_Data_Ref(19) = 9
Ext_User_Prm_Data_Ref(21) = 10
Ext_User_Prm_Data_Ref(23) = 11
Ext_User_Prm_Data_Ref(25) = 12
Ext_User_Prm_Data_Ref(27) = 13
Ext_User_Prm_Data_Ref(29) = 14
Ext_User_Prm_Data_Ref(31) = 15
Ext_User_Prm_Data_Ref(33) = 16
Ext_User_Prm_Data_Ref(35) = 17
Ext_User_Prm_Data_Ref(37) = 18
Ext_User_Prm_Data_Ref(39) = 19
Ext_User_Prm_Data_Ref(41) = 20
Ext_User_Prm_Data_Ref(43) = 21
Ext_User_Prm_Data_Ref(45) = 22
Ext_User_Prm_Data_Ref(47) = 23
Ext_User_Prm_Data_Ref(49) = 24

;============ END of GSD file for VFD Drives =====================

Категория: Delta Electronics | Просмотров: 391 | Добавил: gt7600 | Теги: PROFIBUS, C2000, GSD | Рейтинг: 5.0/1
Всего комментариев: 0
avatar