PLC, HMI, SCADA, INVERTERS, GSD PROFIBUS,
GSDML PROFINET, EDS CanOpen, INDUSTRIAL AUTOMATION

23:12
Delta DVPPF02-SL GSD PROFIBUS DELA0AFE.GSD

Delta PF02-SL GSD PROFIBUS DELA0AFE.GSD

DVPPF02-SL.GSD.zip - DELA0AFE.GSD 

;==========================================================
; GSD-File  for Delta PF02-SL

; Auto_Baud_supp, 12MBaud 
;
;File : DELTAFE.GSD
;
;DATA : 6-Apr-2010
;===========================================================

#Profibus_DP

; ============================
; <Prm-Text-Def-List>
; ============================
PrmText=1
Text(0)="Hold I/O data "
Text(1)="Clear I/O data"
EndPrmText
; ============================
; <Ext-User-Prm-Data-Def-List>
; ============================
ExtUserPrmData=1 "Loss comm with master"
Unsigned8 0 0x00-0x01
Prm_Text_Ref=1
EndExtUserPrmData


; Unit-Definition-List:

GSD_Revision        = 1
Vendor_Name         = "Delta Electronics"
Model_Name          = "DVP PF02-SL"
Revision            = "Rev. 1"
Ident_Number        = 0x0AFE
Protocol_Ident      = 0        ; PROFIBUS DP
Station_Type        = 0        ; DP-slave
FMS_supp            = 0
Hardware_Release    = "V1.0"
Software_Release    = "V1.0"
Redundancy          = 0
Repeater_Ctrl_Sig   = 2        ; TTL
24V_Pins            = 0
Implementation_Type = "SPC3"
Bitmap_Device       = "PF02-SL"
Bitmap_Diag         = "PF02-SL"
Bitmap_SF           = "PF02-SL"
Slave_Family        = 10@TdF@Delta DVP PLC; PLC family

; Supported Communication Speeds:

Auto_Baud_supp      = 1
9.6_supp            = 1
19.2_supp           = 1
93.75_supp          = 1
187.5_supp          = 1
500_supp            = 1
1.5M_supp           = 1
3M_supp             = 1
6M_supp             = 1
12M_supp            = 1
MaxTsdr_9.6         = 60
MaxTsdr_19.2        = 60
MaxTsdr_93.75       = 60
MaxTsdr_187.5       = 60
MaxTsdr_500         = 100
MaxTsdr_1.5M        = 150
MaxTsdr_3M          = 250
MaxTsdr_6M          = 450
MaxTsdr_12M         = 800


; DP_Slave Information:

Freeze_Mode_supp    = 1
Sync_Mode_supp      = 1
Set_Slave_Add_supp  = 0
Min_Slave_Intervall = 1        ; 100 micro-second

; Module-Definitions:

Modular_Station     = 1        ; 0-compact; 1-modular
Max_Module          = 4
Max_Input_Len       = 200
Max_Output_Len      = 200
Max_Data_Len        = 400

Modul_Offset        = 0
Fail_Safe           = 0
Max_Diag_Data_Len   = 16
ORDERNUMBER="PF02-SL"


;specify the user parameters:

 
Max_User_Prm_Data_Len      = 20
User_Prm_Data_Len         = 4
User_Prm_Data            = 0x00,0x00,\
                             0x00,0x00
Ext_User_Prm_Data_Const(0)=0x00,0x00,0x00
Ext_User_Prm_Data_Ref(3)=1                           

; Module Definition List
Module = "1 Word Out        -" 0x60
EndModule
Module = "1 Word In         -" 0x50
EndModule
Module = "2 Word Out        -" 0x61
EndModule
Module = "2 Word In         -" 0x51
EndModule
Module = "4 Word Out        -" 0x63
EndModule
Module = "4 Word In          -" 0x53
EndModule
Module = "8 Word Out        -" 0x67
EndModule
Module = "8 Word In         -" 0x57
EndModule
Module = "16 Word Out       -" 0x6F
EndModule
Module = "16 Word In        -" 0x5F
EndModule
Module = "32 Word Out       -" 0x80,0x5F
EndModule
Module = "32 Word In          -" 0x40,0x5F
EndModule
Module = "64 Word Out       -" 0x80,0x7F
EndModule
Module = "64 Word In          -" 0x40,0x7F
EndModule

Module = "1 Word Out, 1 Word In     -" 0x70
EndModule
Module = "2 Word Out, 2 Word In     -" 0x71
EndModule
Module = "4 Word Out, 4 Word In     -" 0x73
EndModule
Module = "8 Word Out, 8 Word In     -" 0x77
EndModule
Module = "16 Word Out, 16 Word In   -" 0x7F
EndModule
Module = "32 Word Out, 32 Word In   -" 0xC0, 0x5F, 0x5F
EndModule
Module = "64 Word Out, 64 Word In   -" 0xC0, 0x7F, 0x7F
EndModule

;============ END of GSD file for DVP PLC =====================
 

Категория: Delta Electronics | Просмотров: 4 | Добавил: gt7600 | Рейтинг: 5.0/1