XB6-PD2002ST-GSDML-V1.4.zip - XB6PD1.4.GSD XB6-PD0002ST PROFIBUS-DP Coupler kit (with power supply, end cover)

XB6-PD2002ST Coupler Slice I/O user manual - XB6 Series PROFIBUS-DP Slice IO User Manual_V1.06.pdf

Interface Parameters

Protocol PROFIBUS-DP
Max. Number of IO Modules 32
Data Transfer Medium PROFIBUS-DP dedicated cable (shielded twisted pair RS-485 communication cable).
Data Transfer Rates 9.6 Kbps ~ 12 Mbps
Distance Between Stations 9.6 Kbps ~ 187.5 Kbps : ≤1000 m
500 Kbps: ≤400 m
1500 Kbps: ≤200 m
3000 Kbps ~ 12000 Kbps: ≤100 m
Electrical Isolation 500V

Technical Parameters

Power Supply 18~36 VDC
Current Consumption sequentMaximum 1600mA (subsequent IO)
Weight About 300 grams.
Module Size 106*61*47mm
Protect. Class IP20
Operating Temperature -10~60℃
Storage Temperature -20~75℃
Relative Humidity 95%, no condensation
Power Interface Push-in 3pin