DANFOSS GSD PROFIBUS VLT2800 3 MBaud DA010404.GSD

DANFOSS GSD PROFIBUS VLT2800 3 MBaud DA010404.GSD

da010404.gsd.zip 

GSD File Name VLT 2800 Description Ident nr. GSD revision
DA010404.GSD VLT 2800 V0 3 Mbaud (old version) 0404H 01
DA010405.GSD VLT 2800 V0 12 Mbaud (old version) 0405H 01
DA020404.GSD VLT 2800 V0 3 Mbaud (actual version) 0404H 02
DA020405.GSD VLT 2800 V0 12 Mbaud (actual version) 0405H 02
DA030405.GSD VLT 2800 V1 12 Mbaud (actual version) 0405H 03
DA030404.GSD VLT 2800 V1 3 Mbaud (actual version) 0404H 03

;*****************************************************************************
;* The GSD-file is a DP "standard" text file containing
;* the necessary data for configuring DP slaves within a
;* standard DP master.
;* GSD-file: DA010404.GSD
;* GSD-file for Danfoss VLT® 2800 Series with PROFIBUS
;* from PDF VLT2800_Eta-K_PROFIBUS_MG97L202.pdf page 27
;*****************************************************************************
#Profibus_DP
Vendor_Name = "DANFOSS DRIVES A/S";
Model_name = "VLT® SERIES 2800";
Revision = "00";
Ident_Number = 0x0404;
Protocol_Ident = 0;
Station_type = 0;
FMS_supp = 0;
Hardware_Release = "2.0";
Software_Release = "1.00";
9.6_supp = 1;
19.2_supp = 1;
93.75_supp = 1;
187.5_supp = 1;
500_supp = 1;
1.5M_supp = 1;
3M_supp = 1;
6M_supp = 0;
12M_supp = 0;
MaxTsdr_9.6 = 60;
MaxTsdr_19.2 = 60;
MaxTsdr_93.75 = 60;
MaxTsdr_187.5 = 60;
MaxTsdr_500 = 100;
MaxTsdr_1.5M = 150;
MaxTsdr_3M = 250;
Redundancy = 0;
Repeater_Ctr_Sig =0;
24V_Pins = 0;
Freeze_Mode_supp = 1;
Sync_Mode_supp = 1;
Auto_Baud_supp = 1;
Set_Slave_add_supp = 1;
Usr_Prm_Data_Len = 0;
Min_Slave_Intervall = 10;
Modular_Station = 1;
Max_Module = 2;
Max_Input_Len = 28;
Max_Output_Len = 28;
Max_Data_Len = 56;
Max_Diag_Data_Len = 6;
Module = "PPO Typ 1 Module consistent PCD" 0xF3,
0xF1;
EndModule;
Module = "PPO Typ 1 Word consistent PCD" 0xF3,
0x71;
EndModule;
Module = "PPO Typ 2 Module consistent PCD" 0xF3,
0xF5;
EndModule;
Module = "PPO Typ 2 Word consistent PCD" 0xF3,
0x75;
EndModule;
Module = "PPO Typ 3 Module consistent PCD" 0xF1;
EndModule;
Module = "PPO Typ 3 Word consistent PCD" 0x71;
EndModule;
Module = "PPO Typ 4 Module consistent PCD" 0xF5;
EndModule;
Module = "PPO Typ 4 Word consistent PCD" 0x75;
EndModule;
Module = "PPO Typ 5 Module consistent PCD" 0xF3,
0xF9;
EndModule;
Module = "PPO Typ 5 Word consistent PCD" 0xF3,
0x79;
EndModule;